Overview
The GTW1 Air Circuit Breaker is designed to enhance the safety and reliability of electrical systems. It is commonly utilized in industrial, commercial, and public infrastructure settings, effectively mitigating the risks associated with electrical faults. Its compact design and robust capabilities align with international standards, making it suitable for a variety of challenging electrical environments.
Product Features
High Current Capacity
Available in various rated current options, with a maximum capacity of up to 6300A, accommodating diverse load requirements.
Comprehensive Protection
Offers multiple protection features, including overload, short-circuit, and leakage protection, ensuring safety for both equipment and personnel.
Intelligent Monitoring System
Equipped with advanced monitoring modules that continuously track electrical parameters, featuring fault alarms and remote control capabilities for improved management.
Rapid Tripping Technology
Utilizes efficient electromagnetic and thermal protection technologies to quickly disconnect circuits, minimizing damage from electrical faults.
Modular Design
Supports flexible configurations based on user needs, facilitating easy expansion and maintenance for various applications.
Durability and Reliability
Constructed with high-quality materials and advanced manufacturing processes, offering excellent resistance to environmental stresses.
Flexible Installation Options
Can be installed in various settings, such as distribution cabinets or enclosures, adapting to different spatial layouts and simplifying maintenance.
International Compliance
Meets multiple international standards, ensuring product quality and safety, providing users with reliable assurance.
Energy-Efficient Design
Designed to reduce energy consumption, aligning with current trends in energy conservation and sustainability.
Rated Circuit Breaker Ampere Meter, As Shown In Table.
Shell grade rated current InmA | Rated current InA |
2000 | 630/800/1000/1250/1600/2000 |
3200 | 2000/2500/2900/ 3200 |
4000 | 3200/3600/4000 |
6300 | 4000/5000/6300 |
Breakers Of Rated Short Circuit Breaking Capacity And Short-Time Withstand Current, Circuit Breakers Arcing. Distance As "Zero" (That Is, Outside The Circuit Breaker No Flying No Arc), As Shown In Table.
Shell Grade Rated Current Inm A | 2000 | 3200 | 4000 | 6300 | |
Rated limited short-circuit breaking capacity Icu O-CO (KA) | 400V | 80 | 100 | 100 | 120 |
690V | 50 | 65 | 65 | 85 | |
Rated short-circuit making capacity(KA) NX Icu/cosO | 400V | 176/0.2 | 220/0.2 | 220/0.2 | 264/0.2 |
690V | 105/0.25 | 143/0.2 | 143/0.2 | 187/0.2 | |
Rated short circuit breaking capacity Ics O-CO-CO (KA) | 400V | 50 | 65 | 65 | 100 |
690V | 40 | 65 | 65 | 75 | |
Rated short-time withstand current lewv 1S delay 0.4s,O-CO (KA) | 400V | 50 | 65 | 65/80(MCR) | 85/100(MCR) |
690V | 40 | 50 | 50/65(MCR) | 65/75(MCR) | |
Note: the line breaking capacity in the same. |
Circuit Breaker The Maximum Dissipation Power Is 360W. Circuit Breaker Rated Continuous Current In Different Ambient Temperatures, As Shown In Table.
Ambient temperature GTW1 | 630A | 800A | 1000A | 1250A | 1600A | 2000A |
40 | 630A | 800A | 1000A | 1250A | 1600A | 2000A |
50 | 630A | 800A | 1000A | 1250A | 1550A | 1900A |
60 | 630A | 800A | 1000A | 1250A | 1550A | 1800A |
Note: 2500A and above capacity-reducing factor of 0.9, 6300A 4000A did not fall in. |
Had Intelligent Current Controller And Protective Function Of Overcurrent Protection Characteristics
Ir Setting Of Controllers (I/In) And The Error, As Shown In Table.
Long time delay | Short delay | Instantaneous | Ground fault | ||||
Ir1 | Ir2 | Errors | Ir3 | Errors | Ir4 | Errors | |
(0.4-1)In | (0.4-15)In | ±10% | In-50KA(Inm=2000A) In-75K(Inm=3200-4000A) In-100KA(Inm=6300A) | ±150% | Inm=2000-4000A(0.2-0.8) In max 1200A | Inm=6300(0.2~1.0)In | ±10% |
Note: when both (required) three protection, the setting value cannot be crossed. |
Delay Inverse-Time Overcurrent Protection Characteristics I2Ti= (1.5Iri "U (1.05-0.2) Ir 1 Time Is Shown In Table , A Time Error Of ± 15%Note: Tl-Long Time 1.5Irl The Whole Time, Tl Long Delay Time, As Shown In Table.
1.05Irl | 1.3Irl | Setting time of 1.5Irl s | 15 | 30 | 60 | 120 | 240 | 480 |
>2H doesn't work | <1H doesn't work | 2.0Irl time s | 84 | 16.9 | 33.7 | 67.5 | 135 | 270 |
Short Delay Time Overcurrent Protection Characteristicsshort-Delay Over-Current Protection For Setting Time Limits, If Low Expansion For Inverse Time-Time, Its Characteristic: I2Ts = (8Lr) 2Ts,Ts, Designed For General Delay Time When Vhf >8Lrl, Automatically Convert Time Characteristic, Time Characteristic As Shown In Table.
Time Error Is ± 15%
Delay times | Returns the times | ||||||
0.1 | 0.2 | 0.3 | 0.4 | 0.06 | 0.14 | 0.23 | 0.35 |
Mounting dimensions fixed circuit breaker, dimensions (GTW1-2000/3, 2000/4)
Installation dimensions fixed circuit breaker, dimensions (GTW1-3200/3, 3200/4)
Installation drawer sizes and dimensions (GTW1-2000/3, 2000/4)
Installation drawer sizes and dimensions (GTW1-3200/3, 3200/4)
Drawer type circuit breaker mounting sizes and dimensions (GTW1-4000)
Drawer circuit breaker Installation dimensions and Overall dimensions(GTW1-4000/4)
Drawer circuit breaker Installation dimensions and Overall dimensions(GTW1-6300, 6300/4 In: 4000, 5000)
Drawer circuit breaker Installation dimensions and Overall dimensions(GTW1-6300 In: 6300)
Panel bulkhead mounting dimensions figure
I nm | a nm | b mm | c mm |
2000 Series | 306 | 172.5 | 345 |
3200 Series | 366 | 202.5 | 405 |
6300 Series |