12kv
up to 630A
50Hz
1 Piece
Overview
FKN12A-12D/T630-20 indoor high voltage pneumatic load switch-fuse combination (hereinafter referred to as FKN12A-12D load switch) is three-phase high voltage switchgear with rated voltage of 12kV and rated frequency of 50Hz, which is used for the separation and combination of load current, closed-loop current, no-load transformer and cable charging current. Turn off the short circuit current. Load switch equipped with ground switch can withstand short circuit current. FKRN12A-12D/T125-31.5 AC high voltage load switch-fuse combination is indoor high voltage switchgear combined with FN12A-12D load switch and Sport LAJ-2 (XRNT-10) high voltage current-limiting fuse. It can reliably turn on any current up to the short-circuit current, the load switch turns on the working current, the fuse turns on the short-circuit current, and the fuse turns on any overcurrent between the working current and the full short-circuit current. At the same time, the fuse switches off the load switch through its impinger.
Working Conditons
1.Air temperature: -25ºC~+40ºC;
2.Altitude: not more than 1000m;
3.Relative humidity: daily mean no more than 95%, monthly mean no more than 90%.
4.Earthquake intensity: no more than 8 magnitudes;
5.Installation place: no fire, explosion danger, chemical corrosion and violent vibration place;
6.Filth level: 2.
Types of meaning
F | K | N | 12A | - | 12 |
Load switch | Air medium | indoor | Design a sequence number | Rated voltag(KV) |
Overview
FKN12A-12D/T630-20 indoor high voltage pneumatic load switch-fuse combination (hereinafter referred to as FKN12A-12D load switch) is three-phase high voltage switchgear with rated voltage of 12kV and rated frequency of 50Hz, which is used for the separation and combination of load current, closed-loop current, no-load transformer and cable charging current. Turn off the short circuit current. Load switch equipped with ground switch can withstand short circuit current. FKRN12A-12D/T125-31.5 AC high voltage load switch-fuse combination is indoor high voltage switchgear combined with FN12A-12D load switch and Sport LAJ-2 (XRNT-10) high voltage current-limiting fuse. It can reliably turn on any current up to the short-circuit current, the load switch turns on the working current, the fuse turns on the short-circuit current, and the fuse turns on any overcurrent between the working current and the full short-circuit current. At the same time, the fuse switches off the load switch through its impinger.
Working Conditons
1.Air temperature: -25ºC~+40ºC;
2.Altitude: not more than 1000m;
3.Relative humidity: daily mean no more than 95%, monthly mean no more than 90%.
4.Earthquake intensity: no more than 8 magnitudes;
5.Installation place: no fire, explosion danger, chemical corrosion and violent vibration place;
6.Filth level: 2.
Types of meaning
F | K | N | 12A | - | 12 |
Load switch | Air medium | indoor | Design a sequence number | Rated voltag(KV) |
Breaking load current & Close short circuit current
It is used for breaking load current, closed-loop current, no-load transformer and cable charging current, closing short circuit current.
Can withstand short-circuit current
Equipped with grounding switch load switch can withstand short-circuit current.
Arc extinguishing device
When opening, the main shaft drives the piston to compress the air, which makes the compressed air eject from the nozzle at high speed and blow out the arc.
High breaking ability fuse
It has the function of open phase trip,which can cut off short-circuit current and be used as protection equipment.
Breaking load current & Close short circuit current
It is used for breaking load current, closed-loop current, no-load transformer and cable charging current, closing short circuit current.
Can withstand short-circuit current
Equipped with grounding switch load switch can withstand short-circuit current.
Arc extinguishing device
When opening, the main shaft drives the piston to compress the air, which makes the compressed air eject from the nozzle at high speed and blow out the arc.
High breaking ability fuse
It has the function of open phase trip,which can cut off short-circuit current and be used as protection equipment.
PRODUCT SIZE DESCRIPTI
1. Cabinet bracket 2. Disconnector 3. Fuse 4. Insulated tension pole5. Upper bracket 6. Vacum interrupter 7. Static contact 8. Insulator9. Grounding knife 10. Grounding knife spring 11.Opening spring12. The tripping driving device 13. Insulated tension pole 14. Main axle15.Layshaft 16. Adjusting yoke 17. Spring operating mechanism
PRODUCT SIZE DESCRIPTI
1. Cabinet bracket 2. Disconnector 3. Fuse 4. Insulated tension pole5. Upper bracket 6. Vacum interrupter 7. Static contact 8. Insulator9. Grounding knife 10. Grounding knife spring 11.Opening spring12. The tripping driving device 13. Insulated tension pole 14. Main axle15.Layshaft 16. Adjusting yoke 17. Spring operating mechanism
Technical Parameters
No. | project | units | FKN12A-12D | FKRN12A-12D | ||
1 | The rated voltage | KV | 12 | 12 | ||
2 | Rated frequency | Hz | 50 | 50 | ||
3 | Rated current | A | 630 | 125 | ||
4 | Rated insulation level | 1min power frequency | Against the ground, phase | KV | 42 | 42 |
withstand voltage | The isolation of fracture | KV | 48 | 48 | ||
Lightning shock withstand | Against the ground, phase | KV | 75 | 75 | ||
voltage (peak) | The isolation of fracture | KV | 85 | 85 | ||
5 | Load switch | KA | 20 | - | ||
Grounding switch | KA | 20 | 20 | |||
6 | Load switch | S | 4 | - | ||
Grounding switch | S | 2 | 2 | |||
7 | Rated short circuit closing current (peak) | KA | 50 | - | ||
8 | Rated breaking current | Active load breaking current | A | 630 | - | |
Closed-loop breaking current | A | 630 | - | |||
5% active load breaking current | A | 31.5 | - | |||
Cable charging current | A | 10 | - | |||
Turn off the no-load transformer capacity | KVA | 1250 | 1250 | |||
9 | Rated short circuit breaking current (current limiting fuse) | KA | - | 31.5 | ||
10 | Rated transfer current | A | - | 1200 | ||
11 | Mechanical life | next | 2000 | 2000 | ||
12 | Impactor outputs energy | J | - | 1+0.5 |
Technical Parameters
No. | project | units | FKN12A-12D | FKRN12A-12D | ||
1 | The rated voltage | KV | 12 | 12 | ||
2 | Rated frequency | Hz | 50 | 50 | ||
3 | Rated current | A | 630 | 125 | ||
4 | Rated insulation level | 1min power frequency | Against the ground, phase | KV | 42 | 42 |
withstand voltage | The isolation of fracture | KV | 48 | 48 | ||
Lightning shock withstand | Against the ground, phase | KV | 75 | 75 | ||
voltage (peak) | The isolation of fracture | KV | 85 | 85 | ||
5 | Load switch | KA | 20 | - | ||
Grounding switch | KA | 20 | 20 | |||
6 | Load switch | S | 4 | - | ||
Grounding switch | S | 2 | 2 | |||
7 | Rated short circuit closing current (peak) | KA | 50 | - | ||
8 | Rated breaking current | Active load breaking current | A | 630 | - | |
Closed-loop breaking current | A | 630 | - | |||
5% active load breaking current | A | 31.5 | - | |||
Cable charging current | A | 10 | - | |||
Turn off the no-load transformer capacity | KVA | 1250 | 1250 | |||
9 | Rated short circuit breaking current (current limiting fuse) | KA | - | 31.5 | ||
10 | Rated transfer current | A | - | 1200 | ||
11 | Mechanical life | next | 2000 | 2000 | ||
12 | Impactor outputs energy | J | - | 1+0.5 |